How to calculate right parameters for 3-phase two winding transformer Simscape Block?
21 visualizaciones (últimos 30 días)
Mostrar comentarios más antiguos
Artem
el 20 de Jun. de 2024
Comentada: Artem
el 26 de Jul. de 2024
Hi. I have issues with understanding and using parameters for a 3-phase two winding power transformer Simscape Block.
I need to simulate the voltage drop and transformer power losses in a system with a 3-phase two winding transformer. I have transformer parameters from it's datasheet, such as rated power, rated primary and secondary voltages, rated currents. For estimation of impedances I have a short-circuit voltage, short-circuit power, no-load losses. From these I can calcualte winding impedances R1, R2, L1,L2. shunt magnetizing impedances Rm, Lm.
The problem is that I don't know where and how to provide these parameter in Simscape block. The impedances in the block are in power and not clear which applies to what. Does enyone have more clear description of block parameters and their relativity to phisical parameters?
4 comentarios
Umar
el 25 de Jul. de 2024
Hi Artem,
Never mind, I was going to answer your questions but sounds like Milan apparently wanted to share his knowledge. Hope,he can provide a simulation example that he can shared with us.
Respuesta aceptada
Milan Bansal
el 25 de Jul. de 2024
Hi Artem
I understand that you are trying to configure a 3-phase two-winding power transformer in Simscape and are confused about the parameter descriptions and their application.
The reason behind the confusion is the use of per-unit (pu) values for parameters. Here are the steps to clarify and properly set up your transformer parameters:
- Primary and Secondary Winding Resistances: Convert the given resistances to per-unit values based on the rated power and voltage.
- Short-Circuit Parameters: Use the short-circuit voltage and power to estimate the winding impedances.
- No-Load Losses: Use the no-load losses to determine the shunt magnetizing impedances.
Calculate Per-Unit Values:
Calculate the values for (R1, R2, L1, L2, Rm, Lm) using the given specification from the data sheet. Convert these values into per-unit (pu) using the above formulas.
In the Block Parameter, the fields in the "Main" section cab be entered from the datasheet.
For fields in the "Impedences" section, following values can be entered:
- Primary Winding Resistance (pu):
- Secondary Winding Resistance (pu):
- Select "include" for Leakage Reactance and enter the following values.
- Primary Leakage Reactance (pu):
- Secondary Leakage Reactance (pu):
- Select "include" for Magnetizing Resistance and enter the following value.
- Shunt Magnetizing Resistance (pu):
- Select "include" for Magnetizing Reactance and enter the following value.
- Shunt Magnetizing Inductance (pu):
Please refer to the documentation link to learn more about Two-Winding Transformer (Three-Phase)
Hope this helps!