Determining the Nominal mass flow rate

27 visualizaciones (últimos 30 días)
Vanessa Mendez-Valencia
Vanessa Mendez-Valencia el 31 de Oct. de 2024 a las 23:41
Respondida: Yifeng Tang el 1 de Nov. de 2024 a las 22:34
Hello, I am trying to model a reversible heat pump system. I am currently trying to model the coolant loop but I am running into some issues. I am not sure how to determine the Nominal mass flow rate in the System-Level condenser Evaporator block parameters. Any help on how to determine this value would be appreciated.
Thank you!

Respuestas (1)

Yifeng Tang
Yifeng Tang el 1 de Nov. de 2024 a las 22:34
Hello,
First of all, make sure you follow the workflow example in the documentation when modeling a refrigeration system: https://www.mathworks.com/help/hydro/ug/modeling-a-refrigeration-cycle.html
The key idea here is to test each component in individual test harness models before assembling them into a refrigeration loop.
In a test harness model of a condenser or an evaporator, you can drive both the refrigerant side and the external fluid side using reservoirs and ideal flow rate sources. I usually keep the boundary temperature/states and the flow rate the same as the nominal flow rate of the heat exchanger, just to make sure I get the nominal heat transfer I expect.
Now to the question on how to set the nominal values. The nominal values we provide to the block is supposed to describe one set of typical working condition for this heat exchanger. This set of condition may come from
(1) design requirement: e.g. a description like this heat exchanger should allow ?kW heat transfer for coolant at temperature ??deg and refrigerant at ??MPa, given ?? and ?? flow rate for each side. Such requirement usually are derived from the cooling and heating need of the cycle and the temperature conditions it's designed to operate around. If you are following the work flow I mentioned earlier, you should have such information at this stage.
(2) a set of test data or supplier data. Usually you'll have more than one test conditions. I just pick one set somewhere in the middle. The Colburn coefficients will allow you to do a parameter estimation exercise to match other conditions.

Categorías

Más información sobre Thermal Liquid Library en Help Center y File Exchange.

Productos


Versión

R2024a

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by