How are centrifugal pump(TL) outlet flow rate and actual brake power calculated with pump nominal parameters?

40 visualizaciones (últimos 30 días)
Hello,
I am currently working on a data center cooling example using Simscape Fluids. I am trying to understand how the outlet flow rate and the actual brake power of the Centrifugal Pump (TL) are determined based on the Input Angular Velocity (RPM) and the Nominal Parameters and Reference Shaft Speed specified when selecting 'Capacity, head, and brake power at reference shaft speed' within the Centrifugal Pump (TL) block.
I am aware from the block's help documentation that the values are determined according to the affinity laws. However, the equations provided in the help center do not clearly explain how the outlet flow rate is determined based on my specific input RPM relative to the nominal values.
Could someone provide a detailed explanation of the relationship between the Nominal Values, Reference Values, and the values measurable through sensors? And also is there any functions or source codes to expect the output values?
Thank you for your assistance.

Respuesta aceptada

Yifeng Tang
Yifeng Tang el 20 de Nov. de 2024 a las 14:54
In the equation for the reference capacity: , the first term on the RHS is the volumetric flow rate.
If you move that term to the left, this is the equation of flow rate calculated from RPM (ω) and other nominal values.

Más respuestas (0)

Categorías

Más información sobre Simscape Fluids en Help Center y File Exchange.

Productos


Versión

R2024b

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by